MICROfix VP10
GENERALITIES
- Zink-passivated metallic enclosure painted with epossidic dust paint, colour RAL 7035.
- Load-break switch with door interlock.
- Fuses with high breaking power NH00-gG.
- FS17 450/750V self-extinguish cable according to EN 50525 – EN 50575 – EN 50575/A1.
- IP3X protection degree.
- CRM25 single phase self-healing metallized polypropylene capacitor with increased thickness and UN=400V rated voltage.
- Discharge resistance.
- Signal lamp power on.
STANDARDS
Standards (banks) IEC 61439-1/2, IEC 61921
Standards (capacitors) IEC 60831-1/2
Summary
Ue = 400V
UN = 400V
UMAX = 440V
UN = 400V
UMAX = 440V
f = 50 Hz
THDIR% = ≤27%
THDIC% = ≤85%
THDIR% = ≤27%
THDIC% = ≤85%
Part num. |
Power [kvar] Ue=400V |
LBS [A] |
Icc [kA] |
Weight [kg] |
Dimensions [mm] |
Data sheet |
---|---|---|---|---|---|---|
IB5VFF215050987 | 15 | 40 | 50 (Short-circuit withstand current conditioned by the upstream protective device) | 12 | WxDxH 310x200x450 (IP3X) | ![]() |
IB5VFF222550987 | 22.5 | 80 | 50 (Short-circuit withstand current conditioned by the upstream protective device) | 15 | WxDxH 430x250x600 (IP3X) | ![]() |
IB5VFF230050987 | 30 | 80 | 50 (Short-circuit withstand current conditioned by the upstream protective device) | 18 | WxDxH 430x250x600 (IP3X) | ![]() |