MINImatic VP10
GENERALITIES
- Zink-passivated metallic enclosure painted with epossidic dust paint, colour RAL 7035.
- Auxiliary transformer to separate power and auxiliary circuit parts (110V).
- Load-break switch with door interlock.
- Special contactors with damping resistors to limit capacitors inrush current (AC6b).
- FS17 450/750V self-extinguish cable according to EN 50525 – EN 50575 – EN 50575/A1.
- Microprocessor Power Factor Correction relay.
- CRM25 single phase self-healing metallized polypropylene capacitor with increased thickness and UN=400V rated voltage.
STANDARDS
Standards (bank) IEC 61439-1/2, IEC 61921
Standards (capacitors) IEC 60831-1/2
Summary
Ue = 400V
UN = 400V
UMAX = 440V
UN = 400V
UMAX = 440V
f = 50 Hz
THDIR% = ≤27%
THDIC% = ≤85%
THDIR% = ≤27%
THDIC% = ≤85%
Part num. |
Power [kvar] Ue=400V |
Steps Ue=400V |
Electrical steps number |
LBS [A] |
Icc [kA] |
PFC relay |
Weight [kg] |
Dimensions [mm] |
Data sheet |
---|---|---|---|---|---|---|---|---|---|
IF2VFF237550652 | 37.5 | 7,5-2x15 | 5 | 125 | 9 | 5LGA | 81 | WxDxH 420x425x745 (IP3X) | ![]() |
IF2VFF252550652 | 52.5 | 7,5-15-30 | 7 | 125 | 9 | 5LGA | 84 | WxDxH 420x425x965 (IP3X) | ![]() |
IF2VFF275050652 | 75 | 7,5-15-22,5-30 | 10 | 250 | 9 | 5LGA | 94 | WxDxH 420x425x965 (IP3X) | ![]() |
IF2VFF290050652 | 90 | 7,5-15-30-38 | 12 | 250 | 9 | 5LGA | 106 | WxDxH 420x425x1183 (IP3X) | ![]() |
IF2VFF311250652 | 112.5 | 7,5-15-30-60 | 15 | 250 | 9 | 5LGA | 115 | WxDxH 420x425x1183 (IP3X) | ![]() |
IF2VFF313550652 | 135 | 15-2x30-60 | 9 | 400 | 9 | 5LGA | 126 | WxDxH 420x425x1403 (IP3X) | ![]() |
IF2VFF315050652 | 150 | 15-30-45-60 | 10 | 400 | 9 | 5LGA | 132 | WxDxH 420x425x1403 (IP3X) | ![]() |